The endurance limit should be reached simultaneously:
Endurance integrity
Loss of integrity sign: Penetrating cracks or penetrating pores appear on the surface of the pipeline
Thermal insulation resistance
Loss of insulation mark: The average temperature rise at the temperature measurement point on the back of the pipeline reaches 140 ℃, and the temperature rise at any point on the back of the pipeline reaches 180 ℃
6. Test conditions
6.1 Furnace temperature
6.1.1 Temperature rise curve: Measure the average temperature inside the furnace according to the thermocouple specified in 5.5.1.1, and monitor and control it according to the following relationship: T=315 lg (8t+1)
+In equation 20:
T - The average temperature inside the furnace, in degrees Celsius;
T - Time, in minutes.
標準時間-溫度曲線